Features

  • Up to 10 PSI Proof Pressure (Range Dependent)
  • 24 VDC or 24 VAC Excitation
  • High Level 0-5 VDC, 0-10 VDC or 2-Wire 4-20 mA Analog Outputs are Compatible with All Energy Management Systems
  • Fully Protected Against Reverse Wiring
  • Internal Regulation Permits Use with Unregulated DC Power Supplies
  • 1% Accuracy Improves Variable Air Volume System Performance.
  • Optional Accuracies as High as 0.25% FS
  • Fire Retardent Case (UL 94 V-0 Approved)
  • Meets CE Conformance Standards

Applications

  • Heating, Ventilating and Air Conditioning (HVAC)
  • Energy Management Systems
  • Variable Air Volume and Fan Control (VAV)
  • Environmental Pollution Control
  • Static Duct and Clean Room Pressures
  • Oven Pressurization and Furnace Draft Controls

Setra Systems 265 pressure transducers sense differential or gauge (static) pressures and convert this pressure difference to a proportional electrical output. The 265 is offered with a high level 0-5 VDC output or a 4-20 mA output. It is also offered with 0-5 or 0-10 VDC output in the 24 VAC excitation version.

Used in Building Energy Management Systems, these transducers are capable of measuring pressures and flows with the accuracy necessary for proper building pressurization and air flow control.

The 265 Series very low pressure transducers are available for air pressure ranges as low as 0.25 in. WC full scale up to 100 in.WC full scale. Static accuracy is ±1%full scale in normal ambient temperature environments. The units are temperature compensated to less than ±0.033%FS/°F of thermal error over the temperature range of 0°F to +150°F.

The Model 265 utilizes an improved all stainless steel micro-tig welded sensor.

The tensioned stainless steel diaphragm and insulated stainless steel electrode, positioned close to the diaphragm, form a variable capacitor. Positive pressure moves the diaphragm toward the electrode, increasing the capacitance.

A decrease in pressure moves the diaphragm away from the electrode, decreasing the capacitance. The change in capacitance is detected and converted to a linear DC electrical signal by Setra's unique electronic circuit.

The micro-tig welded tension sensor allows up to 10 PSI overpressure (range dependent) with no damage to the unit. In addition, the sensor parts have thermally matched coefficients, which promote improved temperature performance and excellent long-term stability.